Guangzhou Guanda Data Center


华南云计算数据中心集群一期
1st phase of South China Cloud Computing Data Center Cluster

广州观达路数据中心位于广州市黄埔区观达路20号,距广深高速萝岗出口约2公里,是本公司华南云计算数据中心集群的一期项目。观达路数据中心为4层建筑,总面积约2.4万平方米,规划建设2,764个机柜,2018年投产。

Guangzhou Guanda Data Center, the 1st phase project of South China Cloud Computing Data Center Cluster, is located in No. 20 Guanda Road, Huangpu District, Guanghzou, 2km from Luogang Exit of Guangzhou-Shenzhen Highway. With 4 storeys and 24,000㎡ construction area, Guanda Road Data Center will provide 2,764 cabinets in total, and put into operation in 2018.


基础数据
Basic Data

楼层
Floor

模块编号
Module No.

机柜数量(R)
Racks

模块面积()
Module Area

1

101

74

214.4

102

74

211.7

103

46

138

104

110

285.8

105

34

115.2

106

70

208.8

2

201

109

284.4

202

89

238.2

203

89

235.2

204

109

284.4

205

140

341.3

206

140

341.3

207

36

122.4

3

301

109

284.4

302

89

238.2

303

89

235.2

304

109

284.4

4

401

118

312.8

402

96

262

403

96

258.7

404

118

312.8

405

140

341.3

406

110

285.8

407

110

280.3

408

140

341.3

409

79

233.4

410

79

238.2

411

80

235.2

412

82

233.6

合计 Total

2764

7398.7



建设参数
Construction Parameters

  • 地理位置 Location

广东省广州市黄埔区科学城观达路20号
No. 20 Guanda Road, Guangzhou Science City, Huangpu District, Guangzhou, Guangdong






  • 建筑设计 Building

独栋,钢筋混凝土框架结构体系
Detached building, ferroconcrete frame structure

层高一层6.8m,二、三层3.83m,四层4.82m
Story heights: 1st floor: 6.8m, 2nd-3rd floor: 3.83m, 4th floor: 4.82m

地板承重10-15KN/㎡
Loading capacity: 10-15KN/㎡

专用货运电梯及货物卸载区,货梯载重2吨
Freight elevator (2 tons), loading bay


  • 电力系统 Power Supply

双路供电,供电容量37500KVA
Dual paths, power supply capability: 37,500KVA

UPS系统2N冗余配置,满载后备电力15分钟
UPS system with 2N redundant configuration; UPS battery backup time at rated load: 15minutes

柴发采用N+1配置,满载后备供电12小时,与附近供油部门签署协议
Diesel generator with N+1 redundant configuration, operating 12 hours without refueling, and have been signed agreement with the suppliers nearby.

单机柜电力13A~20A,局部可按需改造
Each rack power: 13A~20A; partial rack power could be expanded



  • 冷系统 Air Conditioning

机房使用精密空调调节室内温度和湿度
Precision air-conditioners control IDC temperature and humidity

空调系统采用UPS电源供电,空调冗余N+1
N+1 redundant air-conditioning system powered by UPS

地板下送风,上回风,冷通道封闭(冷热通道严格隔离)
Down-flow air supply, up-flow air return, enclosed cold passages (cold and hot passages are isolated)

水冷,给水中断的情况下系统24小时的正常运行;蓄冷罐15分钟不间断制
Water cooling system operates 24 hours without water supply; cold storage tank provides 15 minutes’ cooling in case chillers fail

  • 消防系统 Fire-Fighting

采用IG541自动气体灭火系统
IG541 automatic gas fire-fighting system

分区相互独立,可以实现分区灭火,此外配备手持式灭火器及空气呼吸器
Independent zone for fire-fighting separately, each zone equipped with handheld extinguisher and air-breather

与空调、新风、门禁、计算机供电和市电等系统联动
Linked air-conditioning, air, access control, computer power supply and city power etc. system

  • 安保系统 Security

可根据用户需求定点增加高清摄像设备
HD cameras could be added as needed on spot

授权门禁系统、红外探测,支持重点区域设施改造
Access control system, infrared detection, renovation for key area infrastructure

人员权限设置,设备安全管理,多层安全防范与管理
Staff permission setting, devices safety management, multi-levels security protection and management

  • 网络环境 Connectivity

按需接入各大运营网络
Backbone network link to China Mobile

多线均万兆对接,可随时根据实际需求进行扩容
Tens of gigabit multiline, scalable as needed

提供144芯裸纤资源,可支持链路改造
144 core bare fiber resource, supporting link renovation



  • 管理服务 Management

7×24小时值守,5 分钟内响应,15分钟内应急处理反馈
7×24 hours guarding, quick response in 5 minutes, emergency processing and feedback in 15 minutes

拥有完备的应急方案、完善的应急管理流程,切实保障业务连续性
Complete emergency solutions and emergency management process to guarantee business continuity